Use 230V A.C. to power the electronic card using the L-N terminals, at a max 50/60Hz frequency.
Use 24V to power the command devices and accessories. Careful! The accessories cannot exceed 37W of overall power.
The card is fi tted with an amperometric device which constantly monitors the motor’s drive. When the gate runs into an obstacle,
the amperometric sensor immediately detects the overload on the drive and so inverts the gate’s movement:
- re-opens the gate while it is in closing-mode (1); - it recloses the gate while is in opening-mode.
(1) Warning: after 3 obstacle detections, the gate stops when in opening-mode and excludes automatic-closing mode; to
regain movement press the command button or use the remote control.
All connections are protected by quick-fuses – see table.
The card handles the following functions:
- Automatic closing after an opening command;
- Warning light pre-fl ashing;
- Obstacle detection when gate is still at any point;
- Constant monitoring of photocell operations.
- Opening/closing;
- Opening/closing in maintained action mode;
- partial opening;
- total stop.
After detecting an obstacle, the photocells will trigger:
- The reopening of a closing gate;
- The partial stop of a moving gate followed by its automatic closing (if this function has been selected).
After an obstacle is detected the sensitive edges will:
- Reopen the gate if it is closing;
- Close the gate if it is opening.
Apposite trimmers regulate:
- The automatic closing’s running time;
- The partial opening;
- The amperometric device’s detection sensitivity, in both normal and brake modes;
- the speed of both the normal gate run and the brake mode run.
6 Control board
6.1 General description
FUSE TABLE
To protect: Fuse:
Motor 8A-F
Control board (line) 1,6A-F
Accessories 1.6A-F
Command devices 1A-F